7.9.3 Setting guidelines
SEMOD172150-4 v7
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
. Note that this function will only use
IBase
value.
Operation
: With the parameter
Operation
the function can be set
On
/
Off
.
Mode
: The voltage and current used for the power measurement. The setting possibilities are
shown in table 37.
Table 37: Complex power calculation
Set value
Mode
Formula used for complex power calculation
L1, L2, L3
* * *
1 1 2 2 3 3L L L L L L
S U I U I U I= × + × + ×
EQUATION1697 V1 EN-US (Equation 57)
Arone
* *
1 2 1 2 3 3L L L L L L
S U I U I= × - ×
EQUATION1698 V1 EN-US (Equation 58)
PosSeq
*
3
PosSeq PosSeq
S U I= × ×
EQUATION1699 V1 EN-US (Equation 59)
L1L2
* *
1 2 1 2
( )
L L L L
S U I I= × -
EQUATION1700 V1 EN-US (Equation 60)
L2L3
* *
2 3 2 3
( )
L L L L
S U I I= × -
EQUATION1701 V1 EN-US (Equation 61)
L3L1
* *
3 1 3 1
( )
L L L L
S U I I= × -
EQUATION1702 V1 EN-US (Equation 62)
L1
*
1 1
3
L L
S U I= × ×
EQUATION1703 V1 EN-US (Equation 63)
L2
*
2 2
3
L L
S U I= × ×
EQUATION1704 V1 EN-US (Equation 64)
L3
*
3 3
3
L L
S U I= × ×
EQUATION1705 V1 EN-US (Equation 65)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
On
/
Off
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
Section 7 1MRK 505 370-UEN D
Current protection
198 Busbar protection REB670
Application manual