12.4.4.3 Configuration setting
M13566-22 v5
If there are no second busbar B and therefore no QB2 disconnector, then the interlocking for
QB2 is not used. The state for QB2, QC21, BC_12 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
• QB2_OP = 1
• QB2QB2_CL = 0
• QC21_OP = 1
• QC21_CL = 0
• BC_12_CL = 0
• VP_BC_12 = 1
If there is no second busbar B at the other side of the transformer and therefore no QB4
disconnector, then the state for QB4 is set to open by setting the appropriate module inputs
as follows:
• QB4_OP = 1
• QB4_CL = 0
12.4.5 Interlocking for bus-section breaker A1A2_BS
IP14154-1 v2
12.4.5.1 Application
M15110-3 v7
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit
breaker between section 1 and 2 according to figure
159. The function can be used for different
busbars, which includes a bus-section circuit breaker.
QA1
WA1 (A1)
QB2
QC4
QB1
QC3
WA2 (A2)
en04000516.vsd
QC2QC1
A1A2_BS
IEC04000516 V1 EN-US
Figure 159: Switchyard layout A1A2_BS
M15111-4 v3
The signals from other bays connected to the module A1A2_BS are described below.
12.4.5.2 Signals from all feeders
M15111-6 v4
If the busbar is divided by bus-section circuit breakers into bus-sections and both circuit
breakers are closed, the opening of the circuit breaker must be blocked if a bus-coupler
Section 12 1MRK 505 370-UEN D
Control
312 Busbar protection REB670
Application manual