connection exists between busbars on one bus-section side and if on the other bus-section
side a busbar transfer is in progress:
Section 1 Section 2
A1A2_BS
B1B2_BS
ABC_LINE
ABC_BC
ABC_LINE
ABC_BC
(WA1)A1
(WA2)B1
(WA7)C C
B2
A2
en04000489.vsd
AB_TRAFOAB_TRAFO
IEC04000489 V1 EN-US
Figure 160: Busbars divided by bus-section circuit breakers
To derive the signals:
Signal
BBTR_OP No busbar transfer is in progress concerning this bus-section.
VP_BBTR The switch status of BBTR is valid.
EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and bus-
coupler bay (ABC_BC) are needed:
Signal
QB12OPTR QB1 or QB2 or both are open.
VPQB12TR The switch status of QB1 and QB2 are valid.
EXDU_12 No transmission error from the bay that contains the above information.
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1
and WA2.
VPBC12TR The switch status of BC_12 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) are needed.
Signal
S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay that contains the above information.
For a bus-section circuit breaker between A1 and A2 section busbars, these conditions are
valid:
1MRK 505 370-UEN D Section 12
Control
Busbar protection REB670 313
Application manual