EasyManua.ls Logo

ABB REB670 Series - Boolean 16 to Integer conversion B16 I; Identification; Application

ABB REB670 Series
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.7 Boolean 16 to Integer conversion B16I
SEMOD175715-1 v1
13.7.1 Identification
SEMOD175721-2 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion B16I - -
13.7.2 Application
SEMOD175832-4 v4
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical)
signals into an integer. It can be used – for example, to connect logical output signals from a
function (like distance protection) to integer inputs from another function (like line differential
protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16
binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of the values
of all the inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. B16I function is designed for receiving up to 16 booleans input locally. If the BLOCK input
is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block B16I.
Name of input Type Default Description Value when
activated
Value when
deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
Section 13 1MRK 505 370-UEN D
Logic
342 Busbar protection REB670
Application manual

Table of Contents

Related product manuals