EasyManua.ls Logo

ABB REB670 Series - Page 183

ABB REB670 Series
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
due to a fault in the station battery system). Note that any backup trip command will inhibit
running of
tStartTimeout
timer.
30ms
OR
START
Current Check
AND
t
t1
TRRET
TRBU
OR
30ms
OR
AND
t
t2 30ms
t
150ms
S
R
Q
AND
NOT
CB Position Check
IEC18001002-1-en.vsdx
IEC18001002 V1 EN-US
Figure 99: Simplified overall logic for LatchedStart
OROR
START
Current Check
CB Position Check
AND
t
t1
t
t1
t
t2
t
t2
TRRET
TRBU
OR
OROR
AND
IEC18001003-1-en.vsdx
IEC18001003 V1 EN-US
Figure 100: Simplified overall logic for FollowStart
OR
START
Current Check
CB Position Check
AND
t
t1
t
t2
TRRET
TRBU
IEC18001004-1-en.vsdx
IEC18001004 V1 EN-US
Figure 101: Simplified overall logic for FollowStart&Mode
RetripMode
: This setting defines how the re-trip function shall operate. Refer to Table 32 for
more details.
1MRK 505 370-UEN D Section 7
Current protection
Busbar protection REB670 177
Application manual

Table of Contents

Related product manuals