due to a fault in the station battery system). Note that any backup trip command will inhibit
running of
tStartTimeout
timer.
30ms
OR
START
Current Check
AND
t
t1
TRRET
TRBU
OR
30ms
OR
AND
t
t2 30ms
t
150ms
S
R
Q
AND
NOT
CB Position Check
IEC18001002-1-en.vsdx
IEC18001002 V1 EN-US
Figure 99: Simplified overall logic for LatchedStart
OROR
START
Current Check
CB Position Check
AND
t
t1
t
t1
t
t2
t
t2
TRRET
TRBU
OR
OROR
AND
IEC18001003-1-en.vsdx
IEC18001003 V1 EN-US
Figure 100: Simplified overall logic for FollowStart
OR
START
Current Check
CB Position Check
AND
t
t1
t
t2
TRRET
TRBU
IEC18001004-1-en.vsdx
IEC18001004 V1 EN-US
Figure 101: Simplified overall logic for FollowStart&Mode
RetripMode
: This setting defines how the re-trip function shall operate. Refer to Table 32 for
more details.
1MRK 505 370-UEN D Section 7
Current protection
Busbar protection REB670 177
Application manual