No. StartMode RetripMode t1 and t2
initiated with
When t1 has
elapsed, TRRET will
When t2 has
elapsed, TRBU
will
be given if
t1 and t2 will be
stopped
(reset) if
21 LatchedStart Always external START always be given current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
t1 and (t2 or t2MPh)
and 150ms expires
and current is below
set level of IPh> or
CBCLD input has
logical value zero
22 FollowStart Off external START never be given current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
23 FollowStart
UseFunction
Mode
external START be given if current
is above set level
of IPh> and higher
than I>BlkCBPos
or CBCLD input
has logical value
one when current
is smaller than
I>BlkCBPos
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
24 FollowStart Always external START be given if
external START is
present
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
external START
disappears
25 FollowStart&
Mode
Off external START
and current
above set level
never be given current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
26 FollowStart&
Mode
UseFunction
Mode
external START
and current
above set level
be given if current
is above set level
of IPh> and higher
than I>BlkCBPos
or CBCLD input
has logical value
one when current
is smaller than
I>BlkCBPos
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
27 FollowStart&
Mode
Always external START
and current
above set level
be given if
external START is
present
current is above set
level of IPh> and
higher than
I>BlkCBPos or
CBCLD input has
logical value one
when current is
smaller than
I>BlkCBPos
current is below set
level of IPh> or
external START
disappears
Section 7 1MRK 505 370-UEN D
Current protection
190 Busbar protection REB670
Application manual