Using PTP for synchronizing the MU
SAM600 VT SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 215: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/
TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc
: is not used as the SW-time and HW-time are connected with each other due to
PTP
SyncLostMode
: set to
Block
to block protection functions if time synchronization is lost
or set to
BlockOnLostUTC
if the protection functions are to be blocked when global
common synchronization is lost
SyncAccLevel
: can be set to
1μs
since this corresponds to a maximum phase angle error of
0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet
configuration/Access point/AP_X:
Operation: On
PTP: On
Two status monitoring signals can be:
SYNCH signal on the MUx function block indicates that protection functions are blocked
due to loss of internal time synchronization to the IED
MUSYNCH signal on the MUx function block monitors the synchronization flag
smpSynch
in the datastream and IED hardware time synchronization.
Section 17 1MRK 505 370-UEN D
Station communication
404 Busbar protection REB670
Application manual