EasyManua.ls Logo

ABB RED650 - Page 100

ABB RED650
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IED
IE D
Protected zone
IEC05000442-2-en.vsdx
IEC05000442 V2 EN-US
Figure 41: One two–winding transformer in the protected zone
IED
IED IED
Protected zone
IEC04000209-2-en.vsdx
IEC04000209 V2 EN-US
Figure 42: One two–winding transformer in the protected zone
Another alternative is with one three-winding transformer in the protected zone,
shown in Figure 43. Observe that in this case, the three-winding power transformer
is seen by the differential protection as two separate power transformers, A and B,
which have one common winding on the HV side.
IEC15000451-2-en.vsdx
IED
IED
A
B
T
T
Protected zone
IEC15000451 V2 EN-US
Figure 43: One three–winding transformer in the protected zone
TraAOnInpCh
M12541-239 v6
This parameter is used to indicate that a power transformer is included in the
protection zone at current terminal X. This can be either a two-winding transformer
Section 6 1MRK 505 393-UEN B
Differential protection
94 Line differential protection RED650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RED650

Related product manuals