EasyManuals Logo

ABB RED650 Applications Manual

ABB RED650
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #171 background imageLoading...
Page #171 background image
A safety margin of 5% for the maximum static inaccuracy and a safety margin of
5% for maximum possible transient overreach have to be introduced. An additional
20% is suggested due to inaccuracy of instrument transformers under transient
conditions and inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 × I
min
EQUATION285 V3 EN-US (Equation 108)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel
line, as shown in Figure
80, should be calculated.
IEC09000025-1-en.vsd
~ ~
Z
A
Z
B
Z
L1
A B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN-US
Figure 80: Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in M A X I
fA
I
fB
I
M
, ,( )³
EQUATION287 V1 EN-US (Equation 109)
Where:
I
fA
and I
fB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
I
s
= 1.3 × I
min
EQUATION288 V3 EN-US (Equation 110)
The IED setting value IN>> is given in percent of the primary base current value,
IBase. The value for IN>> is given by the formula:
1MRK 505 393-UEN B Section 8
Current protection
Line differential protection RED650 2.2 IEC 165
Application manual

Table of Contents

Other manuals for ABB RED650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RED650 and is the answer not in the manual?

ABB RED650 Specifications

General IconGeneral
BrandABB
ModelRED650
CategoryProtection Device
LanguageEnglish

Related product manuals