Setting example
REC
PTP
PTP
Station bus
GPS
SAM600-TS
SAM600-CT
SAM600-VT
PTP
PTP
9-2
PTP
REL
IEC17000069=1=en.vsdx
9-2
9-2
Process bus
IEC17000069 V1 EN-US
Figure 173: Example system
Figure 173 describes an example system. The REC and REL are both using the 9-2
stream from the SAM600, and gets its synch from the GPS. Moreover, the REL
and REC both acts as a boundary clock to provide synch to the SAM600.
On all access points, the PTP parameter is “ON”.
Section 21 1MRK 505 393-UEN B
Basic IED functions
420 Line differential protection RED650 2.2 IEC
Application manual