Parameter Values (Range) Unit Step Default Description
Description Alarm LEDs LED 10 Description of alarm
Alarm LED mode 0=Follow-S
1=Follow-F
2=Latched-S
3=LatchedAck-F-S
0=Follow-S Alarm mode for LED 11
Description Alarm LEDs LED 11 Description of alarm
1) Non-latched mode
2) Non-latched blinking mode
3) Latched mode
4) Latched blinking mode
Table 29: Authorization settings
Parameter Values (Range) Unit Step Default Description
Local override
0=False
1)
1=True
2)
1=True Disable authority
Remote override
0=False
3)
1=True
4)
1=True Disable authority
Local viewer 0 Set password
Local operator 0 Set password
Local engineer 0 Set password
Local admin 0 Set password
Remote viewer 0 Set password
Remote operator 0 Set password
Remote engineer 0 Set password
Remote admin 0 Set password
1) Authorization override is disabled, LHMI password must be entered.
2) Authorization override is enabled, LHMI password is not asked.
3) Authorization override is disabled, communication tools ask password to enter the IED.
4) Authorization override is enabled, communication tools do not need password to enter the IED, except for WHMI which always requires it.
Table 30: Binary input settings
Parameter
Values (Range) Unit Step Default Description
Threshold voltage 18...176 Vdc 2 18 Binary input
threshold voltage
Input osc. level 2...50 events/s 1 30 Binary input
oscillation
suppression
threshold
Input osc. hyst 2...50 events/s 1 10 Binary input
oscillation
suppression
hysteresis
Section 4 1MRS756378 D
Basic functions
114 REF615
Application Manual