Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPORT blocks have
similar instance number or only if all the connected PHASORREPORT blocks
have similar settings for SvcClass and ReportRate. Figure
40 shows the settings for
PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool
(PST).
IEC140000126 V2 EN-US
Figure 40: PMUREPORT settings in PCM600 PST
Figure 41 shows an example of correct connection of SMAI and
PHASORREPORT blocks in ACT where two different SMAI blocks are connected
to different PHASORREPORT blocks with different instance numbers. In this
example, as the PHASORREPORT blocks have different instance numbers and
different settings for SvcClass and ReportRate, a separate SMAI block is used for
each PHASORREPORT block.