Z
load
U
min
3 I
max
×
----------------------
=
EQUATION574 V1 EN-US (Equation 141)
Minimum voltage U
min
and maximum current I
max
are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
As a safety margin is required to avoid load encroachment under
three-phase conditions and to guarantee correct healthy phase IED
operation under combined heavy three-phase load and earth faults,
consider both: phase-to-phase and phase-to-earth fault operating
characteristics.
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
IEC13000273 V1 EN-US (Equation 142)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected
load-impedance angle. For the case when the loop characteristic angle is less than
three times the load-impedance angle, more accurate calculations are necessary
according to equation
143.
RFFwPE Z
R R
X X
load
≤ ⋅ ⋅ ∂ −
⋅ +
⋅ +
⋅ ∂
0 8
2 1 0
2 1 0
. cos sin
min
IEC13000274 V1 EN-US (Equation 143)
Where:
∂ is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the
minimum load impedance.
IEC13000275 V1 EN-US (Equation 144)
Equation 144 is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation 145.
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 231
Application manual