OpModePPZx and OpModePEZx
These settings, two per zone (x=1,2..5&RV), with options {Off, Quadrilateral,
Mho, Offset}, are used to set the operation and characteristic for phase-to-earth and
phase-to-phase faults, respectively.
For example, in one zone it is possible to choose Mho characteristic for the three
Ph-Ph measuring loops and Quadrilateral characteristic for the three Ph-E
measuring loops.
DirModeZx
These settings define the operating direction for Zones Z3, Z4 and Z5 (the
directionality of zones Z1, Z2 and ZRV is fixed). The options are Non-directional,
Forward or Reverse. The result from respective set value is illustrated in figure
222
below, where positive impedance corresponds to the direction out on the protected
line.
IEC05000182-2-en.vsdx
R
X
R
X
R
X
Non-directional Forward Reverse
IEC05000182 V2 EN-US
Figure 222: Directional operating modes of the distance measuring zones 3 to
5
tPPZx, tPEZx, TimerModeZx, ZoneLinkStart and TimerLinksZx
Refer to chapter Simplified logic schemes in Technical Manual for the application
of these settings.
OperationSC
Choose the setting value SeriesComp if the protected line or adjacent lines are
compensated with series capacitors. Otherwise maintain the NoSeriesComp setting
value.
CVTtype
1MRK 506 369-UEN B Section 8
Impedance protection
Line distance protection REL670 2.2 IEC 405
Application manual