4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN-US
Figure 392: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 392, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef (see Section
“Setting of the phase reference channel”) using
PCM600 for analog input channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 18 1MRK 506 369-UEN B
Monitoring
774 Line distance protection REL670 2.2 IEC