CCSPVC1
O:11|T:2.5|I:1
BLOCK FAIL
ALARM
CCSPVC1_CCM_FAIL
CCSPVC1_CCM_ALARM
GUID-A148941E-8D92-4DDB-B497-20582B8FD341 V1 EN
Figure 193: Current circuit supervision function
The fuse failure supervision SEQSPVC1_60-1 detects failures in the voltage
measurement circuits. Failures, such as an open MCB, raise an alarm.
SEQSPVC1
O:30|T:2.5|I:1
BLOCK
CB_CLOSED
DISCON_OPEN
MINCB_OPEN
FUSEF_3PH
FUSEF_V
X120_BI2_CB_CLOSED
SEQSPVC1_60-1_FUSEF_3PH
SEQSPVC1_60-1_FUSEF_U
GUID-ED37B113-A207-4CE2-9C10-72258E3DF7ED V1 EN
Figure 194: Fuse failure supervision function
Circuit-breaker condition monitoring SSCBR1_52CM-1 supervises the switch status
based on the connected binary input information and the measured current levels.
SSCBR1_52CM-1 introduces various supervision methods.
Set the parameters for SSCBR1_52CM-1 properly.
SSCBR1
O:83|T:5|I:1
BLOCK
POSOPEN
POSCLOSE
OPEN_CB_EXE
CLOSE_CB_EXE
PRES_ALM_IN
PRES_LO_IN
SPR_CHR_ST
SPR_CHR
RST_IPOW
RST_CB_WEAR
RST_TRV_T
RST_SPR_T
TRV_T_OP_ALM
TRV_T_CL_ALM
SPR_CHR_ALM
OPR_ALM
OPR_LO
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
CB_CLOSE_COMMAND
CB_OPEN_COMMAND
X120_BI3_CB_OPEN
X120_BI2_CB_CLOSED
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
GUID-91B90F36-39AB-4349-AA02-3D32B2F3A94B V1 EN
Figure 195: Circuit-breaker condition monitoring function
Section 3 1MAC109016-MB C
REF615 standard configurations
154 REF615 ANSI
Application Manual