ABB Relion 615 series - Page 161

ABB Relion 615 series
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OR
O:86|T:2.5|I:11
B1
B2
O
OR6
O:84|T:2.5|I:15
B1
B2
B3
B4
B5
B6
O
OR6
O:85|T:2.5|I:14
B1
B2
B3
B4
B5
B6
O
SSCBR1_52CM-1_TRV_T_OP_ALM
SSCBR1_52CM-1_TRV_T_CL_ALM
SSCBR1_52CM-1_SPR_CHR_ALM
SSCBR1_52CM-1_OPR_ALM
SSCBR1_52CM-1_OPR_LO
SSCBR1_52CM-1_IPOW_ALM
SSCBR1_52CM-1_IPOW_LO
SSCBR1_52CM-1_CB_LIFE_ALM
SSCBR1_52CM-1_MON_ALM
SSCBR1_52CM-1_PRES_ALM
SSCBR1_52CM-1_PRES_LO
SSCBR1_52CM-1_ALARMS
GUID-E99EC5B6-CE3A-4837-A85C-811244F62BE0 V1 EN
Figure 196: Logic for circuit breaker monitoring alarm
Two separate trip circuit supervision functions are included: TCSSCBR1_TCM-1 for
power output X100:PO3 and TCSSCBR2_TCM-2 for power output X100:PO4. Both the
functions are blocked by the master trip TRPPTRC1_86/94-1 and TRPPTRC2_86/94-2
and the circuit breaker open signal.
It is assumed that there is no external resistor in the circuit breaker tripping
coil circuit connected in parallel with the circuit breaker normally open
auxiliary contact.
TCSSCBR1
O:108|T:5|I:1
BLOCK ALARM
TCSSCBR2
O:109|T:5|I:2
BLOCK ALARM
OR
O:110|T:2.5|I:13
B1
B2
O
TCSSCBR1_TCM-1_ALARM
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-2_ALARM
TCSSCBR2_TCM-2_ALARM
TCSSCBR_BLOC KING
TCSSCBR_BLOC KING
TCSSCBR_ALARM
GUID-56B7F3E5-A508-4FB2-9B01-FDB3FFB89CC5 V1 EN
Figure 197: Trip circuit supervision function
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 155
Application Manual