Check the initialization signals of DARREC1_79.
DARREC1
O:56|T:2.5|I:1
INIT_1
INIT_2
INIT_3
INIT_4
INIT_5
INIT_6
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
OPEN_CB
CLOSE_CB
CMD_WAIT
INPRO
LOCKED OUT
PROT_CRD
UNSUC_RECL
AR_ON
READY
ACTIVE
OR6
O:52|T:2.5|I:12
B1
B2
B3
B4
B5
B6
O
OR6
O:53|T:2.5|I:11
B1
B2
B3
B4
B5
B6
O
OR
O:55|T:2.5|I:8
B1
B2
O
X120_BI3_CB_OPEN
DARREC1_79_OPEN_CB
DARREC1_79_CLOSE_CB
PHIPTOC1_50P-3_TRIP
PHHPTOC1_50P-1_TRIP
PHHPTOC2_50P-2_TRIP
NSPTOC2_46-2_TRIP
EFLPTOC1_51G_TRIP
EFHPTOC1_50G-1_TRIP
PDNSPTOC1_46PD_TRIP
ARCSARC1_AFD-1_TRIP
ARCSARC2_AFD-2_TRIP
ARCSARC3_AFD-3_TRIP
NSPTOC1_46-1_TRIP
CBXCBR1_52-1_SELECTED
X110_BI2_EXT_PICIUP_AUTORECLOSE
DARREC1_79_INPRO
DARREC1_79_UNSUC_RECL
GUID-842B6874-C3B5-42F1-9505-54EE6C1C0123 V1 EN
Figure 24: Autoreclosing function
General pickup and trip from all the functions are connected to minimum pulse timer
TPGAPC1 for setting the minimum pulse length for the outputs. The output from
TPGAPC1 is connected to binary outputs.
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 53
Application Manual