7.5 Configuring RCB clients with the IEC 61850
Configuration tool
Add and configure the IEDs before configuring the RCB client. The potential clients
and their communication configuration should be known for a successful RCB client
configuration.
The RCB name is limited to 14 characters or 30 charactecters (without
two-digit index number) depending on which IEC 61850 version is in
use.
1. In the Plant Structure, click the IED node which is RCB server.
2. Click Report Controls tab.
The rows of the Report Controls window show RCBs configured for the IED.
The columns of the Report Controls window show the RCB clients configured
in the PCM600.
3. To add or remove clients for a report control block, click the check-box in the
grid, corresponding to the client and RCB.
Five clients at the maximum can be connected to a RCB.
1MRS757809 C Section 7
Engineering of event reporting with PCM600
REC615 and RER615 93
Engineering Guide