Status or measurand
value has been
received.
Value is followed by
quality attribute?
Proceed to next data entry
Target data value is
defaulted and quality set
to invalid.
Quality is bad?
FALSE
TRUE
Bad quality=
INVALID | RESERVED |QUESTIONABLE |
OVERFLOW | OUT-OF-RANGE | BAD-
REFERENCE | OSCILLATORY | FAILURE
| INCONSISTENT | INACCURATE
TRUE
Old data?Operator blocked?
Operator blocked?
TRUE
FALSE
FALSE
Target data value is
defaulted and quality is
set according to q
attribute.
FALSE
Target data value is
updated and quality is set
according to q attribute.
TRUE
TRUE
FALSE
Target data value is
updated.
Test bit enabled?Receiver in test mode?
FALSE
TRUETRUE
TRUE
TRUE
IEC 61850 Edition 2?
TRUE
FALSEFALSE
GUID-5A73778C-01C5-49BF-9379-34F604E2343B V1 EN
Figure 36: Receiving GOOSE data with quality in the protection relays
5.8 Forcing of GOOSE signals
Application Configuration tool in PCM600 is used for configuring the IED.
5.8.1 Testing of one device
Configuration logic testing is done for individual configurations. GOOSE signals can
be forced using the Signal Monitoring tool.
1MRS757809 C Section 5
GOOSE
REC615 and RER615 57
Engineering Guide