7.3 Creating data sets with the IEC 61850 Configuration
tool
1. Select Plant Structure in the Project Explorer window.
2. Right-click the IED node.
3. Select Client-Server Communication in the drop-down box on the toolbar.
GUID-FF5A846C-7D78-4D14-940D-39D1EFF4B724 V1 EN
Figure 54: Selecting Client-Server Communication
4. Select the Data Sets tab.
5. Right-click the area containing the data set names and select New to add a new
data set.
GUID-26238804-9DF2-4C37-ADC9-65FD63E3DB1D V1 EN
Figure 55: Creating a new data set
6. In the Create New Data Set dialog box, define the LN where to place the data
set (accept preselected “LD0/LLN0”) and give the data set a unique name.
1MRS757809 C Section 7
Engineering of event reporting with PCM600
REC615 and RER615 87
Engineering Guide