Select a proper FC (functional constraint) value for the data attributes
to be added to a data set. If none is selected, that is “(all)” is shown on
the list, it is not possible to add attributes to the data set.
Data set entries for vertical reporting are selected using the data object
level, and entries for GOOSE using the data attribute or data object
level.
8.5 Creating report control blocks with IET600
Configuration properties, such as the attached data set and the buffering and triggering
options of the RCBs are are defined in the RCB editor. A predefined RCB
configuration of a preconfigured IED is a proposed default configuration which can
be adapted according to the requirements.
1. Click an IED node in the IEDs navigation pane.
2. Click the RCB Data tab in the editor pane.
3. Right-click the area containing RCB names and select Insert new row.
4. Define the LN where the RCB is to be placed (preselected LD0/LLN0 is
recommended) and the name for the new RCB.
Use the field chooser to show or hide the properties. For example, the SeqNum,
Entry ID and Reason Code options (set by default in the IED) are hidden by
default.
GUID-1B103FB6-9FE2-4095-9F94-88F1F07FA284 V1 EN
Figure 72: RCB editor
Section 8 1MRS757809 C
Engineering of event reporting with IET600
106 REC615 and RER615
Engineering Guide