Conf.Rev cannot be manually edited. IET600 updates it automatically
to the next multiple of 100 when the configuration changes.
Deleting an RCB does not totally remove it from IET600. Instead, its
status is set to “Deleted” and it is not exported to SCL files. Removing
a data set automatically puts the related RCB to the “Deleted” state.
An RCB cannot be renamed. To rename an RCB, delete it and create
a new RCB with a new name.
The RCB name is limited to 14 characters or 30 charactecters (without
two-digit index number) depending on which IEC 61850 version is in
use.
8.6 RCB client configuration with IET600
To succeed with an RCB client configuration, the potential clients and their
communication configuration should be known. Therefore, the IEDs must be added
and configured to the subnetwork before configuring the RCB client.
The rows of the RCB client editor show IEDs and RCBs and the columns show the
available client IEDs.
If a client IED is not on the same subnetwork as a server IED or RCB,
it cannot be configured as a client.
1MRS757809 C Section 8
Engineering of event reporting with IET600
REC615 and RER615 107
Engineering Guide