Some network routers can block 1588 traffic. Check that all devices
using 1588 time synchronization utilize the same master clock.
SMV data set and SVCB should not be manually added or removed with other tools.
6.3.1 Configuring SMV with the IEC 61850 Configuration tool
The connection between SMV sender and receiver is handled using the IEC 61850
Configuration tool.
1. Start the IEC 61850 Configuration tool.
2. Select Process Bus Communication in the drop-down box on the toolbar.
GUID-0461A422-40DA-4429-B9FA-95CAF5B126EF V1 EN
Figure 41: Selecting Process Bus Communication
The SMV sender and the possible SMV receiver IEDs become visible.
3. Edit the properties and addresses of the sampled value control block.
Some switches do not support multicast filtering with VLAN
value “0” because it means “no VLAN” and VLAN 1 has special
purpose as management VLAN for switches. Recommended
value for VLAN is 2...1001.
Use a unique multicast address for each SVCB. The address
range for sampled values multicast addresses is 01-0C-
CD-04-00-00...01-0C-CD-04-FF-FF.
4. Connect the SMV sender to the receivers.
5. In PCM600, select Write to IED.
If the configuration is updated in a manner that affects the Conf.Rev
value of SVCB, configurations of both SMV sender and all receivers
must be rewritten from PCM600.
Section 6 1MRS757809 C
Process bus and IEEE 1588 time synchronization
66 REC615 and RER615
Engineering Guide