2.1. Define the published GOOSE data and control blocks.
2.2. Define the subscribing IEDs for the GOOSE data.
3. Engineer the IED applications with GOOSE inputs.
5.3.1 Defining IEDs and starting the IEC 61850 Configuration tool
Use PCM600 to define the substation and the IEDs. Before starting the system
engineering, configure the IED settings and logic in PCM600.
For more information, see PCM600 documentation.
1. Create a PCM600 project with all the needed IEDs.
If the substation includes third party IEDs requiring configuring
for horizontal GOOSE communication, instantiate a generic
IEC 61850 IED under the substation in the plant structure and
import the SCL files (ICD/CID) holding the information on
those IEDs. The third party IEDs have separate tools for creating
the ICD/CID/SCD file.
2. Start the IEC 61850 Configuration tool.