In the Data Sets tab and the GOOSE Controls tab, the Clients
column shows all the configured IEDs. For the IED without data sets
and GCBs, however, there is no check box in the grid matrix since the
IED publishes the GOOSE control block to the network.
In the Data Sets tab, the clients are mapped automatically to the
corresponding data sets based on the configuration done in the
GOOSE Controls pane and vice-versa.
5.4 Configuring GOOSE with IET600
See detailed descriptions of the steps in corresponding chapters.
1. Add devices to a PCM600 project.
2. Export the SCD file.
3. Import the SCD file to IET600.
4. Engineer the GOOSE connections between the devices.
4.1. Define the published GOOSE data and control blocks.
4.2. Define the subscribing IEDs for the GOOSE data.
5. Export the SCD file back to PCM600.
6. In PCM600, engineer the IED applications with GOOSE inputs.
Before any configuration, create backups of the PCM600 and
IET600 projects. For example, once an SCD file is imported into
PCM600, the changes cannot be undone except by restoring the
backup.