Loading...
7.4 Creating report control blocks with the IEC 61850
Configuration tool
1. Select the IED node in Plant Structure in Project Explorer.
2. Click the Report Controls tab.
3. Right-click the area containing the existing report control blocks and select New
to add a new report control block.
GUID-184CB65D-000A-4825-965A-406BF345C7AB V1 EN
Figure 58: Adding a new report control block
4. Browse to LLN0 under LD0 to define where to place the report control block.
5. Give a unique name to the report control block.
6. In the drop-down list, select the previously created data set to link with the GCB.
Section 7 1MRS757809 C
Engineering of event reporting with PCM600
90 REC615 and RER615
Engineering Guide

Table of Contents