GUID-BAFE3D00-238E-4187-8B89-3CBF9F1A91D4 V1 EN
Figure 57: Adding data attributes
3. In the data set entry window, select the data attribute to be contained in the data
set.
• Click Append selected to add the data attribute to the end of the data set.
• Click Insert selected to add the data attribute above the selected row in the
data set entries list.
• To remove a data attribute from the data set, select the data attribute in the
data set entries pane and click Removed selected.
Reporting datasets can include status and measurement type of data. Also
configuration and setting values can be added to datasets in case required.
Data set entries for vertical reporting are selected using the data object
level, and entries for GOOSE using the data attribute or data object
level.
The default data set for SMV sending is fixed and may not be
modified.
1MRS757809 C Section 7
Engineering of event reporting with PCM600
REC615 and RER615 89
Engineering Guide