8.1.2 Attaching IEC 61850 clients to a bus with IET600
1. Click the Communication tab in the navigation pane.
2. Click the Subnetworks tab in the editor pane.
3. In the Subnetworks grid, select the bus from the Subnetwork list to attach the
IEC 61850 client to the bus.
An alternative way is to drag the client in the Communication tab to the correct
subnetwork.
GUID-EA889F86-E189-4890-8308-5EB713778999 V1 EN
Figure 66: Defining bus connection properties for IEC 61850 clients
4. Repeat the steps to attach all five default clients in the project to the bus.
By default, the IEDs' bus connections are ready-made when the configuration work is
started and need not to be set separately. After the client bus connections are created,
the event clients appear in the RCB Clients tab.
8.2 IET600 user interface
IET600 user interface is divided into sections, that is, panes for navigating and
displaying the project data.
Section 8 1MRS757809 C
Engineering of event reporting with IET600
100 REC615 and RER615