GUID-EB4EE24C-111F-45E7-BFC4-FF6A1DB93F3F V1 EN
Figure 74: Semi-automatic configuring of RCB clients
1. Configure the default clients which are used by the rule-based RCB generation
to automatically configure RCB clients.
Use buttons on the RCB client editor.
Clear All removes all default clients
Configure Empty fills out only default clients for those IEDs that have no
clients configured yet
Configure All deletes all existing default clients and fills them out
afterwards
2. Configure the RCBs clients.
The default clients must be configured before configuring RCB clients
otherwise the automatic RCB client configuration does not work. Use buttons on
the RCB client editor.
Clear All removes all RCB clients
Configure Empty copies the default client configuration of this IED to its
RCBs (only for those RCBs that have no clients configured yet)
Configure All deletes the existing RCB clients and copies the default
client configuration of this IED to its RCBs
IET600 updates the Enabled Clients configuration value of the RCBs
automatically based on the configuration made in the RCB client
editor. In addition, IET600 always reserves one extra engineering
client. For example, when configuring three RCB clients, the Enabled
Clients value of that RCB is “4”.
1MRS757809 C Section 8
Engineering of event reporting with IET600
REC615 and RER615 109
Engineering Guide