GUID-CA85B312-AD8E-4BF0-9AFB-95171B1A4962 V1 EN
Figure 24: Naming a GOOSE control block
4. Browse to LLN0 under LD0 to define where the GOOSE control block is to be
placed.
5. Give a unique name to the GOOSE control block.
6. In the Attached Dataset drop-down list, select the previously created data set.
After creating the GOOSE control block, edit its properties and addresses. Edit
at least MAC Address and APP-ID.
GUID-1F5C7FB1-7245-4678-8770-C694F6F92DB7 V1 EN
Figure 25: GOOSE control block properties
To set the visibility of the GoCB columns, click the upper-left
icon of the table and select or clear the check boxes in the Field
Chooser dialog.
Section 5 1MRS757809 C
GOOSE
44 REC615 and RER615
Engineering Guide