It is possible to reset the GOOSE communication diagnostics counters via
Monitoring/I/O Status/Communication/GSELPRT1/Monitoring/Reset
counters and via the IEC 61850 communication by writing TRUE to the
RsCnt.Oper.ctlVal attribute under GSELPRT1.
Table 7: Diagnostics data objects
Data object Description Diagnostics information
FrRxCnt Received messages When increasing, the protection relay is receiving GOOSE
messages.
FrTxCnt Transmitted messages When increasing, the protection relay is sending GOOSE
messages.
RxStCnt Received state changes Received GOOSE messages with a new stNum value
RxSeqCnt Received sequence
number
Received GOOSE retransmissions or heartbeat cycle
messages with a new sequence number
RxTestCnt Received frames with
test bit
Received GOOSE frames with the test flag on
StWrnCnt State errors Number of notified state number jumps
SeqWrnCnt Sequence errors Number of notified sequence number jumps
RxTmOutC
nt
Receiver time-outs Number of notified peer device time-outs
ConfErrCnt Received ConfRev
mismatches
When increasing, there is a mismatch between the received
GOOSE frame information and the used GOOSE
configuration.
NdsComCnt
Received frames with
Needs Commissioning
One peer device Indicates that its configuration is not valid or
up-to-date.
DSErrCnt Errors in received data
set
Received data are syntactically wrong, or there are less data
in received data set than expected.
Alm Receiver alarm Alarm signal value connected to the event and application
logic. It is active when one peer device is in time-out.
GOOSE Alarm is activated in the receiver device in certain situations.
Time-out
Configuration revision mismatch
Error in the received data set
The Needs Commissioning bit is active in the received message