Section 2 DNP3 data mappings
2.1 Overview
This document describes the DNP3 data points and structures available in REM615
Ver.4.0. The data points are unmapped as a default on the DNP3 level.The point
lists describe a superset of all data available through the standard configuration A,
B, and C including the optional functionalities. The names of the standard
configurations are ME01, ME02 and ME03 respectively.
The point tables show all the available DNP3 data points in the IEDs. The data
objects in the point tables are listed based on the AFL function block and data
object IEC61850 names.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. These assignments can be modified later.
Analog values are provided with default scalings. The scalings can be freely
modified by the user.
This list represents the superset of DNP3 points. The actual set of available points,
meaning the actual set of available applications, is determined by the IED's ordercode.
2.2 Supported functions
Table 2: Supported functions in REM615
IEC 61850
ME01 ME02 ME03
PHLPTOC1
PHIPTOC1
EFLPTOC1
EFHPTOC1
DEFLPDEF1
PHPTUV1
PSPTUV1
NSPTOV1
FRPFRQ1
FRPFRQ2
MNSPTOC1
MNSPTOC2
LOFLPTUC1
Table continues on next page