2.3.1.3 LD0.ARCSARC3 Fault arc protection stage 3
Table 6: LD0.ARCSARC3 Fault arc protection stage 3
IEC 61850 name SA name Description Values
LD0.ARCSARC31
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC31
.Op.general OPERATE Operate 1=Operate
2.3.1.4 CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
Table 7: CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
IEC 61850 name SA name Description Values
CTRL.CBCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.CBCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.CBXCBR1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
CTRL.CCBRBRF1
.OpEx.general TRBU Failure ext.trip 1=Failure
.OpIn.general TRRET Operate, re-trip 1=Operate
.Str.general CB_FAULT_AL Start, timer running 1=Start
2.3.1.5 CTRL.Dxxxxx1 Controllable disconnector (1)
Table 8: CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name
SA name Description Values
CTRL.DCCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
Section 2 1MRS756880 C
DNP3 data mappings
14 REM615
Point List Manual