2.3.3.17 LD0.PEMMTR1 Power measurement and accumulated power values
Table 91: LD0.PEMMTR1 Power measurement and accumulated power values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.PEMMTR1
.DmdVArh.actVal ER_RV_ACM Forward reactive energy 0…1e10 R 0,1E10,0,1E10
.DmdWh.actVal EA_RV_ACM Forward active energy 0…1e10 R 0,1E10,0,1E10
.SupVArh.actVal ER_FWD_ACM Reverse reactive energy 0…1e10 R 0,1E10,0,1E10
.SupWh.actVal EA_FWD_ACM Reverse active energy 0…1e10 R 0,1E10,0,1E10
.TotPF.instMag PF_INST Average power factor -1…1 R -1,1,-100,100
.TotW.instMag P_INST Active power 0…999999 R 0,999999,0,999999
.TotVA.instMag S_INST Apparent power 0…999999 R 0,999999,0,999999
.TotVAr.instMag Q_INST Reactive power 0…999999 R 0,999999,0,999999
2.3.3.18 DR.RDRE1 Disturbance recorder values
Table 92: DR.RDRE1 Disturbance recorder values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
DR.RDRE1
.FltNum.stVal - Number of recordings 0…65535 R 0,65535,0,65535
.MemUsed.stVal - Rec. memory used 0…100 [%] R 0,100,0,100
2.3.3.19 LD0.RESCMMXU1 Residual current (1)
Table 93: LD0.RESCMMXU1 Residual current (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.RESCMMXU1
.A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] R 0,40,0,4000
2.3.3.20 LD0.RESVMMXU1 Residual voltage (1)
Table 94: LD0.RESVMMXU1 Residual voltage (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.RESVMMXU1
.PhV.res.instCVal.mag U0_INST Residual voltage
0.00..4.00
[xUn] R 0,4,0,400