IEC 61850 ME01 ME02 ME03
PEMMXU1   ● ●
XRGGIO130 o o  
FMMXU1   ● ●
● = available in the device variant, o = optionally available in the device variant
2.3  Point list for REM615 Ver.4.0 ME01-03
2.3.1  Binary inputs
Table 3: Explanations of the binary input table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible for example in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
Value Meaning of the input states.
2.3.1.1  LD0.ARCSARC1 Fault arc protection stage 1
Table 4: LD0.ARCSARC1 Fault arc protection stage 1
IEC 61850 name
SA name Description Values
LD0.ARCSARC11      
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC11      
.Op.general OPERATE Operate 1=Operate
2.3.1.2  LD0.ARCSARC2 Fault arc protection stage 2
Table 5: LD0.ARCSARC2 Fault arc protection stage 2
IEC 61850 name
SA name Description Values
LD0.ARCSARC21      
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC21      
.Op.general OPERATE Operate 1=Operate
1MRS756880 C Section 2
DNP3 data mappings
REM615 13
Point List Manual