IEC 61850 name SA name Description Values
.OpNumAlm.stVal OPR_ALM CB operations alarm 1=Alarm
.OpNumLO.stVal OPR_LO CB operations lockout 1=Lockout
.PresAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
.PresLO.stVal PRES_LO Low pressure lockout 1=Lockout
.SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 1=Alarm
2.3.1.46 LD0.STTPMSU1 Motor startup supervision
Table 49: LD0.STTPMSU1 Motor startup supervision
IEC 61850 name SA name Description Values
LD0.STTPMRI1
.Op.general OPR_STALL Thermal stress operate 1=Operate
LD0.STTPMSS1
.Op.general OPR_IIT Stalling operate 1=Operate
.Str.general MOT_START Startup in progress 1=In progress
2.3.1.47 LD0.TCSSCBR1 Trip circuit supervision (1)
Table 50: LD0.TCSSCBR1 Trip circuit supervision (1)
IEC 61850 name
SA name Description Values
LD0.TCSSCBR1
.CirAlm.stVal ALARM Supervision alarm 1=Alarm
2.3.1.48 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 51: LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name
SA name Description Values
LD0.TCSSCBR2
.CirAlm.stVal ALARM Supervision alarm 1=Alarm
2.3.1.49 LD0.TRPPTRC1 Global conditioning (1)
Table 52: LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name Description Values
LD0.TRPPTRC1
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
1MRS756880 C Section 2