2.3.1.13 LD0.EMSGAPC1 Emergency start
Table 16: LD0.EMSGAPC1 Emergency start
IEC 61850 name SA name Description Values
LD0.EMSGAPC1
.Str.general ST_EMERG_ENA Emergency start 1=Start
2.3.1.14 LD0.FRPFRQ1 Frequency protection (1)
Table 17: LD0.FRPFRQ1 Frequency protection (1)
IEC 61850 name SA name Description Values
LD0.FRPTRC1
.Str.general START Stage start 1=Start
LD0.FRPTOF1 Overfrequency
.Op.general OPR_OFRQ -Operate 1=Operate
LD0.FRPTUF1 Underfrequency
.Op.general OPR_UFRQ -Operate 1=Operate
LD0.FRPFRC1 Frequency gradient
.Op.general OPR_FRG -Operate 1=Operate
2.3.1.15 LD0.FRPFRQ2 Frequency protection (2)
Table 18: LD0.FRPFRQ2 Frequency protection (2)
IEC 61850 name
SA name Description Values
LD0.FRPTRC2
.Str.general START Stage start 1=Start
LD0.FRPTOF2 Overfrequency
.Op.general OPR_OFRQ -Operate 1=Operate
LD0.FRPTUF2 Underfrequency
.Op.general OPR_UFRQ -Operate 1=Operate
LD0.FRPFRC2 Frequency gradient
.Op.general OPR_FRG -Operate 1=Operate
2.3.1.16 LD0.JAMPTOC1 Stalled motor protection
Table 19: LD0.JAMPTOC1 Stalled motor protection
IEC 61850 name
SA name Description Values
LD0.JAMPTOC1
.Op.general OPERATE Stage operate 1=Operate
1MRS756880 C Section 2
DNP3 data mappings
REM615 17
Point List Manual