2.3.1.6 CTRL.Dxxxxx2 Controllable disconnector (2)
Table 9: CTRL.Dxxxxx2 Controllable disconnector (2)
IEC 61850 name SA name Description Values
CTRL.DCCILO2
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.DCCSWI2
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.DCXSWI2
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.1.7 CTRL.Exxxxx1 Controllable earth switch (1)
Table 10: CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name SA name Description Values
CTRL.ESCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.1.8 CTRL.CCRDIF1 Current circuit failure protection
Table 11: CTRL.CCRDIF1 Current circuit failure protection
IEC 61850 name
SA name Description Values
CTRL.CCRDIF1
.Alm.stVal FAIL Fail Alarm 1=Alarm
.Op.general ALARM Fail Operate 1=Operate
1MRS756880 C Section 2
DNP3 data mappings
REM615 15
Point List Manual