2.3.3.8 CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2 bit) position
values
Table 82: CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2 bit) position values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI2
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.9 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values
Table 83: CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.10 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values
Table 84: CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI2
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.11 CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position
values
Table 85: CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position values
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.ESXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.12 LD0.DNPGGIO1 Active parameter setting group
Table 86: LD0.DNPGGIO1 Active parameter setting group
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.DNPGGIO1
.ActSG.stVal - Active setting group 1…6 R 1,6,1,6