2.3.3.3 LD0.CSMSQI1 Sequence of currents
Table 77: LD0.CSMSQI1 Sequence of currents
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.CSMSQI1 Sequence of currents
.SeqA.c1.instCVal.mag I1_INST -Positive magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c2.instCVal.mag I2_INST -Negative magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.SeqA.c3.instCVal.mag I3_INST -Zero magnitude 0.00..40.0 [xIn] R 0,40,0,4000
2.3.3.4 CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
Table 78: CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.DCSXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.5 CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
Table 79: CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.DCSXSWI2
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.6 CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values
Table 80: CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.DCSXSWI3
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.7 CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position
values
Table 81: CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position values
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.DCXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
1MRS756880 C Section 2