2.3.1.9  LD0.CMMXU1 Phase currents (1) limit supervision
Table 12: LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name SA name Description Values
LD0.CMMXU1      
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.1.10  LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
Table 13: LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
IEC 61850 name SA name Description Values
LD0.DEFLPTOC1   Low stage (1)  
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.1.11  LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - high stage 1
Table 14: LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault protection - high stage 1
IEC 61850 name
SA name Description Values
LD0.EFHPTOC1   High stage (1)  
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.1.12  LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - low stage 1
Table 15: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1
IEC 61850 name
SA name Description Values
LD0.EFLPTOC1   Low stage (1)  
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
Section 2 1MRS756880 C
DNP3 data mappings
16 REM615
Point List Manual