ABB REM615 - LD0.CMMXU1 Phase Currents (1) Limit Supervision; LD0.DEFLPDEF1 Directional Earth-Fault Protection - Low Stage 1; LD0.EFHPTOC1 Non-Directional Earth-Fault and Sensitive Earth-Fault Protection - High Stage 1; LD0.EFLPTOC1 Non-Directional Earth-Fault and Sensitive Earth-Fault Protection - Low Stage 1

ABB REM615
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.1.9 LD0.CMMXU1 Phase currents (1) limit supervision
Table 12: LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name SA name Description Values
LD0.CMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.1.10 LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
Table 13: LD0.DEFLPDEF1 Directional earth-fault protection - low stage 1
IEC 61850 name SA name Description Values
LD0.DEFLPTOC1 Low stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.1.11 LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - high stage 1
Table 14: LD0.EFHPTOC1 Non-directional earth-fault and sensitive earth-fault protection - high stage 1
IEC 61850 name
SA name Description Values
LD0.EFHPTOC1 High stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.1.12 LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault
protection - low stage 1
Table 15: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1
IEC 61850 name
SA name Description Values
LD0.EFLPTOC1 Low stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start