DNP3 device profile document
○ Configurable ○ When device restarts
○ Only certain objects ○ When status flags change
○ Sometimes (attach explanation)
○ ENABLE/DISABLE UNSOLICITED
function codes supported
No other options are permitted.
Default counter object/variation: Counters roll over at:
● No counters reported ● No counters reported
○ Configurable ○ Configurable (attach explanation)
○ Default object
Default variation:
○ 16 bits
○ Point-by-point list attached ○ 32 bits
○ Other value: _______
○ Point-by-point list attached
Sends multi-fragment responses:
● Yes
○ No
○ Configurable
Sequential file transfer support:
Append file mode ○ Yes ● No
Custom status code strings ○ Yes ● No
Permissions field ○ Yes ● No
File events assigned to class ○ Yes ● No
File events send immediately ○ Yes ● No
Multiple blocks in a fragment ○ Yes ● No
Max number of files open 0
● = Selected,○ = Not selected
3.2 DNP3 implementation table
The following table identifies which object variations, function codes and
qualifiers the IED supports in both request messages and response messages. For
static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08
are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are
responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28
are always responded.
1MRS756880 C Section 3
DNP3 protocol implementation
REM615 41
Point List Manual