EasyManua.ls Logo

ABB REM615 - LD0.MNSPTOC2 Negative-Sequence Overcurrent Protection for Motors (2); LD0.MPTTR1 Motor Thermal Overload Protection; LD0.MVGAPC1 Multipurpose Binary Inputs (1); LD0.MVGAPC2 Multipurpose Binary Inputs (2)

ABB REM615
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.1.30 LD0.MNSPTOC2 Negative-sequence overcurrent protection for
motors (2)
Table 33: LD0.MNSPTOC2 Negative-sequence overcurrent protection for motors (2)
IEC 61850 name SA name Description Values
LD0.MNSPTOC2
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.1.31 LD0.MPTTR1 Motor thermal overload protection
Table 34: LD0.MPTTR1 Motor thermal overload protection
IEC 61850 name SA name Description Values
LD0.MPTTR1
.AlmThm.general ALARM Thermal alarm 1=Alarm
.Op.general OPERATE Thermal operate 1=Operate
.StrInh.general BLK_RESTART Block restart 1=Restart
2.3.1.32 LD0.MVGAPC1 Multipurpose binary inputs (1)
Table 35: LD0.MVGAPC1 Multipurpose binary inputs (1)
IEC 61850 name
SA name Description Values
LD0.MVGAPC1
.Q1.stVal - Input 1 signal 0/1=Off/On
.Q2.stVal - Input 2 signal 0/1=Off/On
.Q3.stVal - Input 3 signal 0/1=Off/On
.Q4.stVal - Input 4 signal 0/1=Off/On
.Q5.stVal - Input 5 signal 0/1=Off/On
.Q6.stVal - Input 6 signal 0/1=Off/On
.Q7.stVal - Input 7 signal 0/1=Off/On
.Q8.stVal - Input 8 signal 0/1=Off/On
2.3.1.33 LD0.MVGAPC2 Multipurpose binary inputs (2)
Table 36: LD0.MVGAPC2 Multipurpose binary inputs (2)
IEC 61850 name
SA name Description Values
LD0.MVGAPC2
.Q1.stVal - Input 1 signal 0/1=Off/On
.Q2.stVal - Input 2 signal 0/1=Off/On
.Q3.stVal - Input 3 signal 0/1=Off/On
Table continues on next page
1MRS756880 C Section 2
DNP3 data mappings
REM615 21
Point List Manual

Table of Contents

Other manuals for ABB REM615

Related product manuals