2.3.2.13 LD0.SSCBR1 Reset signals of CB condition monitoring
Table 73: LD0.SSCBR1 Reset signals of CB condition monitoring
IEC 61850 name SA name Description Type
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
2.3.3 Analog inputs
Table 74: Explanations of the analog input table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible for example in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
Values The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S Scaling type selected as default. Default “R” means ratio scaling. See the DNP
communication protocol manual for details.
Arg 1, 2, 3, 4 Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP communication protocol manual for details.
2.3.3.1 CTRL.CBCSWI1 CB 4-pole (2 bit) position value
Table 75: CTRL.CBCSWI1 CB 4-pole (2 bit) position value
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
CTRL.CBCSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.2 LD0.CMMXU1 Phase currents (1)
Table 76: LD0.CMMXU1 Phase currents (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.CMMXU1 Phase-to-ground current
.A.phsA.instCVal.mag I_INST_A -phsA magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsB.instCVal.mag I_INST_B -phsB magnitude 0.00..40.0 [xIn] R 0,40,0,4000
.A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] R 0,40,0,4000