10 | RMC-100| 2105552MNAE
1 System description
The Remote Modular Controller (RMC-100) provides measurement, automation, monitoring, alarming,
asset data management, control, and data logging applications. A single RMC-100 controller can
manage automation, liquids and gas measurement, and asset data concentration for very large
production and transmission facilities.
1.1 Features overview
The RMC provides backward-compatible functionality based on ABB Totalflow software,
communications, and I/O technologies. The existing process foundation and the new enhanced
technology manage liquid and gas measurement, automation, and asset data concentration for large-
scale production and transmission facilities. It is scalable down to a single-board RTU footprint for
smaller systems.
The RMC supports I/O and communication expansion.
The RMC supports dual, backward-compatible TFIO buses, doubling the I/O module capacity to 44
modules.
The table below provides the general specifications for the RMC.
Table 1-1: General specifications
Specification
Operating voltage
range
output connections of both the onboard and TFIO modules depend on the
Nominal power
Weight
Dimensions
Width
7.56 inches (19.20 cm)
Height
8.31 inches (21.11 cm)
Depth
1.72 inches (4.37 cm)
Installed Depth
On DIN rail 1.79 inches (4.55 cm)
Input/Output
Maximum battery
capacity
Mounting
Operating
temperature
-40 °C to 70 °C (-40 °F to 158 °F) when no battery is used
Electromagnetic
compatibility
FCC CFR 47, Part 15, Subpart B, Class A (FCC Emissions)
IECS-03, Issue 4, CAN/CSA-CEI/IEC CISPR 11 Class A (Canada ITE Emissions)
EMC Directive
2004/108/EC
Immunity EN 61326-1 to:
EN 61000-4-2, ESD, 8 kV Air, 4 kV Contact
EN 61000-4-3, RFI, 10 V/m
EN 61000-4-4, EFT, 2 kV to DC, 1 kV to Signals
EN 61000-4-6, Conducted, 0.15-80 MHZ, 3 Vrms
Hazardous location
certification
(North America)
the United States of America:
UL No. 61010-1: "Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use - Part 1: General Requirements"
ANSI/ISA 12.12.01: "Non-incendive Electrical Equipment for Use in Class I and
II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations."
ANSI/UL 60079-0: "Explosive Atmospheres Part 0: Equipment General
Requirements"
ANSI/UL 60079-15: "Explosive atmospheres Part 15: Equipment protection by
type of protection 'n' "