48 | RMC-100| 2105552MNAE 
Figure 4-3: Synchronize date and time 
9.  Click Yes. The RMC calendar clock synchronizes with the laptop date and time. 
10.  Configure the RMC. 
•  To use Ethernet, complete steps in the following section.  
•  To use USB, remain on the current USB connection and proceed to section 4.3.1 
Configure 
the station. 
4.2.2  Using the Ethernet ports 
The startup configuration of the RMC requires first-time local communication. Establish a connection 
between a PC or laptop and the device over Ethernet after installation and power-on sequence is 
complete.  
The Ethernet ports auto-configure to adapt to the Ethernet cable type. Table 4-2
 displays the cabling 
specifications for Ethernet ports. 
Table 4-2: Ethernet cabling 
(with Ethernet 10/100 BaseT ports) 
Required cabling termination 
(connectors) or adaptors 
ABB part 
number 
Host system (operator laptop or computer)  
Straight-through Ethernet CAT 5 
cable with RJ-45 connectors at 
both ends. 
Maximum 
distance:  
100 meters 
(328 feet) 
Network device (Ethernet hub, switch or router)  
Other Totalflow devices: additional RMCs, flow 
computers, and analyzers 
 
Local TCP/IP communication over Ethernet requires correct IP configuration and addressing. The RMC 
Ethernet factory default configuration supports initial connection with pre-configured IP parameters for 
convenience.  
The RMC is configured as a 2-port Ethernet switch from the factory. Figure 4-4
 shows the default 
Ethernet mode as viewed from PCCU. Ethernet is configured in 1 Network mode, therefore devices 
connected to either port communicate on the same subnet. A single default IP address (169.254.0.11) 
is ready for initial local communication using either of the 2 ports. To use either port, set the Ethernet 
State to Enable.