Figure 3-13: TFIO module pins 
3.6.3  Connect third-party serial modules 
Third-party Ethernet-to-serial modules add serial communication ports to connect additional external 
devices such as XMVs and transmitters. For instructions about using MOXA
®
 modules, the third-party 
modules used to expand serial capacity to the controller, see section 10 
Serial port expansion with 
MOXA® modules. 
3.7  Power the RMC 
This section describes two modes for powering the controller. Select one mode: 
–  Battery mode: a 12 volt battery with a charger supplies power (see section 3.7.2). 
–  External power mode: an external power source supplies power (see section 3.7.3). 
Follow the instructions for the appropriate power mode, then continue to section 3.8, Enable lithium 
battery backup. 
 
– Equipment damage. The maximum input voltage fo
r legacy TFIO modules is 12 
Vdc.
 
 
 
Externally fuse the power input for the load. This consists of the equipment, 
plus any external devices powered by the RMC. The wire gauge should be appropriate (in some 
applications a minimum of 16 
AWG gauge is advisable). 
3.7.1  Power-on sequence 
The RMC power-on sequence initiates when power is connected. The LCD displays the following 
information as the controller completes its startup: 
–  ABB TOTALFLOW RMC-100 identifies the controller name and model 
–  BOOT 2105412-XXX indicates the version of the boot software 
–  OS 2105411-XXX indicates the version of the operating system 
–  Super CAP Charged indicates if the super capacitor is charged (see section 2.2.9) 
–  APP 2105457-XXX indicates the version of the flash