10.1  Configuration overview 
The example described in this section includes a MOXA module and an ABB XMV as the measurement 
transmitter with which the RMC communicates. This scenario assumes: 
–  RMC COMM 1 and COMM 2 are unavailable or additional serial capacity is necessary. 
–  The RMC is connected to a network. There is also an available connection for the MOXA module 
on the same network. 
–  Valid IP addresses are available for both the RMC and the MOXA module. 
 
Both the RMC and the MOXA module must have valid IP addresses to 
communicate. Devices such as the XMV 
transmit measurement data in real-time, so the TCP/IP 
connection between the RMC and the Ethernet
-to-serial device must be reliable (the IP 
configuration must remain intact all the time). To prevent loss of IP configuration, configure both 
devices with sta
tic IP addresses. 
Static IP address configuration does not depend on network connectivity as dynamic addressing 
does. Use of DHCP for device IP addressing in this scenario could cause measurement data loss 
during a network outage or disconnection. Network 
connectivity should never affect local 
communication with measurement or control peripherals.
 
 
Table 10-1: Configuration for connection to Ethernet-to-serial devices 
Ethernet-to-Serial device  
interfaces 
Verify that the Ethernet interface is 
enabled (In PCCU Entry mode, on the 
navigation tree, select Communications 
then the Networking tab): Ensure the 
State of the interface is set to Enable.   
Consult MOXA documentation for details to 
enable the Ethernet interface on the 
module.  
 
Parameters 
Change default IP parameters for valid IP 
parameters and restart the interface. 
In PCCU Entry mode, on the navigation 
tree select Communications then the 
Networking tab. Enter valid IP 
parameters (obtained from the network 
administrator). They must be on the same 
subnet as the Ethernet-to-serial device. 
Consult MOXA documentation for details to 
configure static addressing (ensure DHCP 
is disabled) and manually configure valid 
IP parameters (obtained from the network 
administrator). Must be on the same 
subnet as the RMC. 
 
In PCCU Entry mode, on the navigation 
tree select Communications, then on the 
Communication Setup tab, add the 
communication application appropriate for 
the serial device type and configure 
desired serial parameters. Serial port 
parameters must match those on the 
MOXA module and serial devices. See 
section 
10.3 Configure the RMC Ethernet 
interface to support MOXA®. 
Consult MOXA documentation for serial 
port configuration. Make sure to match 
serial interface parameters to the attached 
serial device. 
 
 
 For other third-party devices, consult vendor documentation for steps to 
interface, and configure network (IP) and serial port parameters. Details of 
configuration depend on the implementation of vendors, but standard Ethernet and serial interfaces 
should be interoperable. 
 
10.2  Configure the MOXA
®
 module  
This procedure describes how to configure the MOXA
®
 module to operate with the RMC. This includes 
manually setting up the module’s IP network parameters (static addressing), the serial port 
configuration, and the mode of operation.