2105552MNAE | RMC-100 | 73
Figure 4-37: TFIO-B Module List
10. For specific module setup, expand either TFIO-A Modules or TFIO-B Modules on the navigation
tree and select the desired modules for further configuration.
Click Help on specific TFIO module screens for additional information and
parameter description. The I/O Interface has online topics that explain configuration options
available on the PCCU screens.
5 Advanced setup
Customize the RMC to meet individual site needs. Complete these steps in PCCU Expert view. Click
View on the PCCU32 menu and select Expert from the drop-down list.
5.1 Configure the LCD backlight
The RMC LCD backlight is configurable. Change default settings (Figure 5-1) on the Station Setup tab:
– Select one or more triggers that enable the backlight.
– Select the trigger that turns the backlight on.
– Define the number of seconds per timeout. The backlight remains on for display activity during
the timeout period.
LCD Backlight Status is a read-only field that shows whether the backlight is off or on. The backlight is
always off if it is disabled.
To set up the backlight:
1. On the Station Setup screen, scroll down to LCD Backlight (Figure 5-1
). Click Help for
additional information about the Station Setup tab.
Figure 5-1: LCD backlight default settings
2. Select Off or On from the LCD Backlight Enable drop-down list.
3. Select an option from the LCD Backlight Trigger drop-down list: On, Off, Always On, On for
Local Connections, or On for Push Buttons.