2105552MNAE | RMC-100 | 73
Figure 4-37: TFIO-B Module List
10. For specific module setup, expand either TFIO-A Modules or TFIO-B Modules on the navigation
tree and select the desired modules for further configuration.
IMPORTANT NOTE:
Click Help on specific TFIO module screens for additional information and
parameter description. The I/O Interface has online topics that explain configuration options
available on the PCCU screens.
5 Advanced setup
Customize the RMC to meet individual site needs. Complete these steps in PCCU Expert view. Click
View on the PCCU32 menu and select Expert from the drop-down list.
5.1 Configure the LCD backlight
The RMC LCD backlight is configurable. Change default settings (Figure 5-1) on the Station Setup tab:
Select one or more triggers that enable the backlight.
Select the trigger that turns the backlight on.
Define the number of seconds per timeout. The backlight remains on for display activity during
the timeout period.
LCD Backlight Status is a read-only field that shows whether the backlight is off or on. The backlight is
always off if it is disabled.
To set up the backlight:
1. On the Station Setup screen, scroll down to LCD Backlight (Figure 5-1
). Click Help for
additional information about the Station Setup tab.
Figure 5-1: LCD backlight default settings
2. Select Off or On from the LCD Backlight Enable drop-down list.
3. Select an option from the LCD Backlight Trigger drop-down list: On, Off, Always On, On for
Local Connections, or On for Push Buttons.